Replacing the EBM(s)
About this task
CAUTION:
The weight of this part or unit is more than 55 kg (121.2 lb). It takes specially
trained persons, a lifting device, or both to safely lift this part or unit. (C011)
To replace the EBM(s):
Procedure
1.
Unplug the EBM power cable and battery detection cable from the UPS. If
additional EBM(s) are installed, unplug the EBM power cable and battery
detection cable from each EBM.
2.
Replace the EBM(s). See “Recycling the used equipment” on page 53 for proper
disposal.
Note:
A small amount of arcing might occur when connecting EBMs. This is
normal and will not harm personnel. Insert the EBM cable into the battery
connector quickly and firmly.
3.
Plug the EBM cable(s) into the battery connector(s). Up to four EBMs can be
connected to the UPS.
4.
Verify that the EBM connections are tight and that adequate strain relief exists
for each cable.
5.
Connect the battery detection cable(s) to the connector of the UPS and of the
EBM(s).
Testing a new battery pack
About this task
To test a new battery pack:
Procedure
1.
Allow the batteries to charge for 48 hours.
2.
Press any button to activate the menu options.
3.
Select
Control
>
Start a battery test
.
The UPS starts a battery test if the battery pack is fully charged, the UPS is in
Normal mode with no active alarms, and the bypass voltage is acceptable.
50
Installation and User's Guide
Summary of Contents for RT11.0VA
Page 2: ......
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 98: ...80 Installation and User s Guide ...
Page 100: ...82 Installation and User s Guide ...
Page 101: ......
Page 102: ...Part Number 00WA361 Printed in USA 1P P N 00WA361 ...