Table 15. Weights and dimensions (Power Module) (continued)
Model (Power
Module)
Dimensions D x W x H (mm /
inch)
Weight (lb / kg)
8K Power Module
(KX)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
42 / 19
11K Power Module
(PX)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
51 / 23
11K Power Module
(KX)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
46 / 21
Minimum rack depth for UPS with MBP: 900mm (35.4 inches)
Table 16. Weights and dimensions (EBM)
Model (EBM)
Dimensions D x W x H (mm /
inch)
Weight (lb / kg)
5594-9BX
680 x 440 x 130 (26.8 x 17.3 x 5.1)
143 / 65
Table 17. Environmental and safety standards
EMC certifications
IEC/EN 62040-1: 2008
IEC/EN 62040-2: 2006 Cat. C2
IEC/EN 62040-3: 2011
IEC 60950-1
EMC (Emissions)
- for output
cable < 10m
CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
EMC (Immunity)
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
Agency markings
CE / C-Tick
Operating temperature
0 to 40°C (32 to 104°F) in Online mode, with linear
derating for altitude
Note:
Thermal protection switches load to Bypass in
case of overheating.
64
Installation and User's Guide
Summary of Contents for RT11.0VA
Page 2: ......
Page 18: ...xvi Installation and User s Guide ...
Page 22: ...4 Installation and User s Guide ...
Page 86: ...68 Installation and User s Guide ...
Page 98: ...80 Installation and User s Guide ...
Page 100: ...82 Installation and User s Guide ...
Page 101: ......