PDU types explained
The following section discusses the differences between an Lenovo Basic PDU, a
Monitored PDU, and a Switched and Monitored PDU.
Basic PDUs (non-Monitored)
A Basic PDU does not have the ability to collect power statistics or have the outlets
controlled remotely.
Monitored PDUs
A Monitored PDU (also known as PDU+) has the ability to collect power statistics.
These statistics can be viewed through the PDUs web interface or via System
Management tool such as Lenovo Systems Director, Active Energy Manager (AEM).
A Monitored PDU does not have the ability to control the outlets remotely.
Switched and Monitored PDUs
A Switched and Monitored PDU has the ability to collect power statistics. These
statistics can be viewed through the PDUs web interface or via System Management
tool such as Lenovo Systems Director, Active Energy Manager (AEM).
A monitored PDU has the ability to control the outlets remotely (switch individual
outlets on/off) via the PDUs web interface or via Lenovo Active Energy Manager
(AEM).
All monitored (and switched and monitored) PDUs collect the below data at a PDU
level and outlet level:
PDU Input Statistics:
Input Voltage (V) - Present Value, Min, Max
Input Current (A) - Present Value, Min, Max
Power Factor (0.0 – 1.0) - Present Value, Min, Max
Input Frequency (Hz) - Present Value, Min, Max
Input Power (W) - Present Value, Min, Max
Cumulative Kilowatt Hours – Present Value, Min, Max
Individual Outlet Statistics:
Output Voltage (V) - Present Value, Min, Max
Output Current (A) - Present Value, Min, Max
Output Power Factor (0.0 – 1.0) - Present Value, Min, Max
Load Watts (W) - Present Value, Min, Max
Cumulative Kilowatt Hours – Present Value, Min, Max
9
Summary of Contents for System x PDU
Page 7: ... 16A Three Phase Delta Power Calculations 219 SUPPORT 220 HELPFUL LINKS 221 7 ...
Page 45: ... Three phase 39Y8941 PDU 45 Figure 19 Outlet and amperage ...
Page 67: ... Three phase 71762NX PDU 67 Figure 31 Outlets and amperage ...
Page 68: ... Single phase model 71762NX PDU 68 Figure 32 Outlets and amperage ...
Page 95: ... The following figures show the PDU outlets and amperage 95 Figure 51 Outlets and amperage ...
Page 106: ... Three phase 39M2816 106 Figure 57 Outlets and amperage ...
Page 107: ... Single phase 39M2816 107 Figure 58 Outlets and amperage ...
Page 119: ... Three phase 46M4004 119 ...
Page 120: ... Single phase 46M4004 120 Figure 64 Outlets and amperage ...
Page 131: ... Single phase operation 131 Figure 71 Outlets and amperage ...
Page 171: ... 171 Figure 107 IEC309 3P N G 16A plug ...
Page 193: ... IEC 309 Pin Decode The following table is a break down of the Hubbell HBL part number 193 ...
Page 194: ... 194 ...
Page 195: ... 195 ...
Page 198: ... 50A Three Phase Delta Power Calculations 30A Three Phase Delta Power Calculations 198 ...
Page 199: ... 32A Three Phase Delta Power Calculations 16A Three Phase Delta Power Calculations 199 ...
Page 200: ... Support 200 ...