Figure 30. DIMM installation
Step 6. Make sure that the small tabs on the retaining clips engage the notches on the DIMM. If there is a
gap between the DIMM and the retaining clips, the DIMM has not been correctly installed. Press
the DIMM firmly into the connector, and then press the retaining clips toward the DIMM until the
tabs are fully seated.
Note:
Retaining clips on the DIMM connectors must be in the closed position to install the air
baffle.
After you install the DIMM, complete the following steps:
1. Install the air baffle (see “Install the air baffle” on page 32).
Attention:
To maintain proper system cooling, do not operate the compute node without an air baffle
installed over the DIMM connectors.
2. Install the compute node cover (see “Install the compute node cover” on page 43 ).
3. Install the compute node into the chassis (see “Install the compute node in the chassis” on page 25 ).
4. Power on the compute node.
Fabric connector replacement
Use the following information to remove and install a fabric connector.
Remove a fabric connector
Use this information to remove a fabric connector.
Before you remove the fabric connector, complete the following steps:
1. Read “Safety” on page iii and “Installation Guidelines” on page 21 to ensure that you work safely.
2. Power off the corresponding compute node that you are going to perform the task on.
3. Remove the compute node from the chassis (see “Remove the compute node from the chassis” on page
4. Carefully lay the compute node on a flat, static-protective surface, orienting the compute node with the
bezel pointing toward you.
5. Remove the compute node cover (see “Remove the compute node cover” on page 42).
6. Obtain a long shank #1 Phillips screwdriver.
.
Hardware replacement procedures
49
Summary of Contents for ThinkSystem SN550
Page 1: ...ThinkSystem SN550 Compute Node Maintenance Manual Machine Type 7X16 ...
Page 8: ...vi ThinkSystem SN550 Compute Node Maintenance Manual ...
Page 28: ...20 ThinkSystem SN550 Compute Node Maintenance Manual ...
Page 124: ...116 ThinkSystem SN550 Compute Node Maintenance Manual ...
Page 128: ...120 ThinkSystem SN550 Compute Node Maintenance Manual ...
Page 137: ......
Page 138: ...Part Number SP47A10572 Printed in China 1P P N SP47A10572 1PSP47A10572 ...