7
RG-MCMET
N2 Points
4.1 Metasys N2 Point Map
Table 3: Metasys N2 Point Map for MC3000 Series Drives
Point
Type
1
Point
#
Description (Point Name)
Read (R)/
Override (R/O)
Point
Units
Decimal
Places
MIN
Value
MAX
Value
Default
Value
1
1
Parameter Version
R
--
0
--
--
143
2
1
2
Software Version
R
--
0
--
--
043
2
1
3
Software Revision
R
--
0
--
--
05
2
1
4
Drive Config/Size
R
--
0
0
57
--
1
5
Drive Class
R
--
0
--
--
65
1
6
Total Runtime (RUNTIME HRS)
R
hrs
0
0
--
1
7
Total Runtime (RUNTIME MIN)
R
min
0
0
--
1
8
Operational Status (RUN STATUS)
R
--
0
0
10
--
1
9
Load Percent (LOAD PERCENT)
R
%
0
150
180
180
1
10
Motor Voltage (MOTOR VOLTS)
R
VAC
0
1
11
Present Fault (FAULT)
R
--
0
0
23
0
1
12
Recorded Fault 1
R
--
0
0
23
0
1
13
Recorded Fault 2
R
--
0
0
23
0
1
14
Recorded Fault 3
R
--
0
0
23
0
1
15
Recorded Fault 4
R
--
0
0
23
0
1
16
Recorded Fault 5
R
--
0
0
23
0
1
17
Recorded Fault 6
R
--
0
0
23
0
1
18
Recorded Fault 7
R
--
0
0
23
0
1
19
Recorded Fault 8
R
--
0
0
23
0
1
20
PID Feedback (PID FEEDBACK)
R
PID
0
Note 3
Note 3
Note 3
1
21
PID Setpoint Command (PID SETPOINT)
R
PID
0
Note 3
Note 3
Note 3
1
22
Actual Speed (ACTUAL FREQ)
R
Hz
2
0
12000
--
2
01
Fault Condition (OK.FAULT)
R
--
0
OK
FLT
OK
3
01
Command Speed (COMMAND SPD)
R/O
Hz
2
0
120.00
20.00
3
02
Keypad Command Speed (CMD KEY SPD)
R/O
Hz
2
0
120.00
20.00
3
03
Normal Acceleration (ACCEL)
R/O
sec
1
*
3600.0
30.0
3
04
Normal Deceleration (DECEL)
R/O
sec
1
*
3600.0
30.0
3
05
Local PID Command
R/O
PID
0
Note 3
Note 3
Note 3
3
06
Control Mode
R/O
--
0
4
01
History
R/O
--
0
0 (maintain)
1 (clear)
0
4
02
Start/Stop Drive (CMD RUN.STOP)
R/O
--
0
0 (stop)
1 (start)
0
4
03
Speed Control Auto/Manual
R/O
--
0
0 (auto)
1 (manual)
0
4
04
Clear Present Fault (CLEAR FAULT)
R/O
--
0
0
1 (clear)
NOTES:
1. Point Types: 1 = Analog Input; 2 = Binary Input; 3 = Analog Output; 4 = Binary Output
2. Current Value of the parameter version, software version and software revision.
3. Units, MIN/MAX Values: for this point are defined via Drive Parameters #31, 75 and 76 respectively.
Refer to notes in sections 4.2 and 4.4.
* Refer to MC3000 Installation & Operation Manual (M301)
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com