CANopen
6
Parameter setting
6-45
L
BA2175 EN 2.0
L-C23xx (for 9300 servo PLC)
Possible settings
Code
Subcode
Index
Lenze
Selection
Data type Name
L-C1810
-
22765
d
= 58ED
h
-
-
VS
Software product code
L-C1811
-
22764
d
= 58EC
h
VS
Software date
L-C2120
-
22455
d
= 57B7
h
0
0 = No command
1 = Code L-23XX update and CAN
re-initialisation
≡
Reset node
2 = Code L-C23XX update
10 = Reading of L-C2356/1...4
11 = Reading of L-C2357
12 = Reading of L-C2375
13 = Reading of L-C2376 ... L-C2378
14 = Reading of L-C2382
15 = Not assigned
FIX32
AIF control byte
L-C2121
-
22454
d
= 57B6
h
0
0
[1]
255 FIX32
AIF status byte
L-C2350
-
56D1
h
= 22225
d
1
1
[1]
63 FIX32
Node address
L-C2351
-
56D0
h
= 22224
d
0
0 = 500 kbit/s, 1 = 250 kbit/s
2 = 125 kbit/s, 3 = 50 kbit/s
4 = 1000 kbit/s, 5 = 20 kbit/s
6 = 10 kbit/s
FIX32
Baud rate
L-C2352
-
56CF
h
= 22223
d
0
0 = Slave operation
1 = Master operation
FIX32
Master / slave operation
L-C2353
/1 ... /3
56CE
h
= 22222
d
0
0 = Addressing to CANopen
1 = Addressing to L-C1854/L-C2354
2 = Addressing to LENZE system bus
3 = Addressing to CANopen index
14Xx
h
/18XX
h
FIX32
CAN-INx/CAN-OUTx
addressing
L-C2354
/1 ... /6
56CD
h
= 22221
d
/1: 129
/2: 1
/3: 257
/4: 258
/5: 385
/6: 386
0
[1]
1663 FIX32
CAN-IN/CAN-OUT
selective addressing
L-C2355
/1 ... /6
56CC
h
= 22220
d
-
0
[1]
2047 FIX32
Resulting identifier
display
L-C2356
/1 ... /5
56CB
h
= 22219
d
1:
3000 ms
2 .. 5:
0 ms
0
[1 ms]
65535 FIX32
Boot-up and cycle times
L-C2357
/1 ... /4
56CA
h
= 22218
d
3000 ms 0
[1 ms]
65535 FIX32
Monitoring time
L-C2359
-
56C8
h
= 22216
d
-
0
[1]
1023 U16
DIP-switch position
display
L-C2367
-
56C0
h
= 22208
d
128
0
[1]
2047 FIX32
Sync Rx identifier
L-C2368
-
56BF
h
= 22207
d
128
0
[1]
2047 FIX32
Sync Tx identifier
L-C2373
/1 ... /3
56BA
h
= 22202
d
1
1
[1]
240 FIX32
CAN-IN1 ... CAN-IN3 sync
rate
L-C2374
/1 ... /3
56B9
h
= 22201
d
1
1
[1]
240 FIX32
CAN-OUT1 ... CAN-OUT3
sync rate
L-C2375
/1 ... /3
56B8
h
= 22200
d
/1: 0
/2: 1
/3: 1
0
[1]
3 FIX32
CAN-OUT1 ... CAN-OUT3
Tx mode
L-C2376
/1 ... /4
56B7
h
= 22199
d
65535 0
[1]
65535 FIX32
CAN-OUT1 masks
L-C2377
/1 ... /4
56B6
h
= 22198
d
65535 0
[1]
65535 FIX32
CAN-OUT2 masks
L-C2378
/1 ... /4
56B5
h
= 22197
d
65535 0
[1]
65535 FIX32
CAN-OUT3 masks
L-C2382
/1 ... /5
56B1
h
= 22193
d
0
0
[1]
2
0: No response
1: Controller inhibit
2: Quick stop
FIX32
Monitoring responses
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com