CANopen
6
Parameter setting
6-10
L
BA2175 EN 2.0
6.2.2
Examples
6.2.2.1
Parameter reading
The heatsink temperature (43
°
C) C061 is to be read from the controller using address 5 and
parameter channel 1.
•
Identifier calculation
Identifier parameter channel 1 to controller
= 1536 + controller address
Identifier
= 1536 + 5 = 1541
•
Command read request (request to read a parameter from the drive
Command
= 40
hex
•
Index calculation
Index = 24575 - code number - 2000 (PS - 1)
Index = 24575 - 61 - 2000
ú
0 = 24514 = 5FC2
hex
Telegram to drive:
Identifier
Command
Index Low
Byte
Index High
Byte
Subindex
Data 1
Data 2
Data 3
Data4
1541
40
hex
C2
hex
5F
hex
00
00
00
00
00
Telegram from drive
Identifier:
Parameter channel 1 of controller (=1408) + controller address = 1413
Command:
Read response to read request with the current value of 43
hex
Index of read request
5FC2
hex
Subindex:
0
Data 1 to Data 4:
43 ° C
S
10.000 = 430.000 = 00 06 8F B0
Identifier
Command
Index Low
Byte
Index High
Byte
Subindex
Data 1
Data 2
Data 3
Data4
1413
43
hex
C2
hex
5F
hex
00
B0
hex
8F
hex
06
hex
00
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com