CANopen
6
Parameter setting
6-21
L
BA2175 EN 2.0
6.3.4.2
Status word for 82XX and 8200 vector
820X
821x,822x
8200vector default setting
0
Actual parameter set
0 = Parameter set 1 or 3 active
1 = Parameter set 2 or 4 active
Actual parameter set
0 = Parameter set 1 or 3 active
1 = Parameter set 2 or 4 active
DCTRL-PAR-B0
1
IMP (pulse inhibit)
0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
IMP (pulse inhibit)
0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
DCTRL1-IMP
2
I
max
(current limit reached)
0 = Current limit not reached
1 = current limit reached
I
max
(current limit reached)
0 = Current limit not reached
1 = current limit reached
MCTRL1-IMAX
3
not assigned
f
d
= f
dset
0 = f
d
≠
f
dset
1 = f
d
= f
dset
MCTRL1-RFG1=NOUT
4
f
d
= f
dset
0 = f
d
≠
f
dset
1 = f
d
= f
dset
RFG on = RFG off
0 = RFG on
≠
RFG off
1 = RFG on = RFG out
NSET1-RFG1-I=0
5
Qmin (f
d
≤
f
dQmin
)
0 = Qmin not active
1 = Qmin active
Qmin (f
d
≤
f
dQmin
)
0 = Qmin not active
1 = Qmin active
PCTRL1-QMIN
6
f
d
+ 0 (act. frequency = 0)
0 = f
d
≠
0
1 = f
d
+ 0
f
d
+ 0 (act. frequency = 0)
0 = f
d
≠
0
1 = f
d
+ 0
DCTRL1-NOUT=0
7
Ctrl. inhibit (controller inhibit)
0 = controller not inhibited
1 = controller inhibited
Ctrl. inhibit (controller inhibit)
0 = controller not inhibited
1 = controller inhibited
DCTRL1-CINH
8...11 !controller status
0 = Controller initialization
8 = Error active
!controller status
0 = Controller initialization
1 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error active
!controller status
0 = Controller initialization
1 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error active
12
Overtemperature warning
0 = No warning
1 = Warning
Overtemperature warning
0 = No warning
1 = Warning
DCTRL1-OH-WARN
13
U
Gmax
(DC-bus overvoltage)
0 = No overvoltage
1 = overvoltage
U
Gmax
(DC-bus overvoltage)
0 = No overvoltage
1 = overvoltage
DCTRL1-OV
14
Direction of rotation
0 = CW rotation
1 = CCW rotation
Direction of rotation
0 = CW rotation
1 = CCW rotation
DCTRL1-CCW
15
Ready
0 = not ready for operation
1 = ready for operation
Ready
0 = not ready for operation
1 = ready for operation
DCTRL1-RDY