CANopen
6
Parameter setting
6-30
L
BA2175 EN 2.0
6.4.1
Description of implemented objects
6.4.1.1
1000
hex
: Device type
Reading of the device type and its functionality
Index
[
hex
]
Subindex
Name
Data type
Authorisation
1000
0
Device type
U32
ro
Bit assignment in telegram data
5th byte
6th byte
7th byte
8th byte
U32
LSB
Controller profile number
MSB
Additional information
6.4.1.2
1001
hex
: Error register
Reading of the error register
Index
[
hex
]
Subindex
Name
Data type
Authorisation
1001
0
Error register
U8
ro
Bit assignment in telegram data byte (U8)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
0
0
0
0: No TRIP
1: Controller TRIP/ error in
CANopen module
For error analysis see L-C0161
in corresponding Operating
Instructions
6.4.1.3
1003
hex
: Pre-defined error field
Error history
Index
[
hex
]
Subindex
Name
Data type
Authorisation
1003
0
Recording numbers of error
U8
rw
1003
1
Standard error field
U32
r0
This object shows that errors occurred in the module and the basic unit.
•
Subindex 0: Number of saved error messages
•
Subindex 1: Error list
Error messages (U32) consis of a 16-bis error code and a 16-bit manufacturer-specific
information field.
Tip!
The “ standard error field” (subindex 0) will be completely deleted if it is overwritten with “ 0” .