CANopen
6
Parameter setting
6-32
L
BA2175 EN 2.0
6.4.1.7
100A
hex
: Manufacturer’s software version
Controller and module software version
Index
[hex]
Subindex
Name
Data type
Authorisation
100A
0
Manufacturer software version Vis. string
{11 characters}
const
6.4.1.8
100C
hex
: Guard time
Monitoring time
Index
[hex]
Subindex
Name
Data type
Authorisation
100C
0
Guard time
U16
rw
The guard time is indicated in [ms].
If guarding is not to be supported, the default setting of 0 should not be changed.
6.4.1.9
100D
hex
: Life time factor
Index
[hex]
Subindex
[hex]
Name
Data type
Authorisation
100D
0
Life time factor
U8
rw
If the guarding function, which results from guard time and life time factor, is not to be supported,
the default setting of 0 should not be changed. For further information see chapter 6.1.2.1.
6.4.1.10
1010
hex
: Store parameters
Parameter storage in the EEPROM.
Index
[hex]
Subindex
Name
Data type
Authorisation
1010
0
Store parameters
U32
ro/rw
1010
1 ... 3*
Store parameters
U32
ro/rw
The subindexes 1, 2 and 3 are presently not supported.
Parameter storage
Error messages occur when
•
storage is incorrect (in bytes 5 ...8): 0606 0000
hex
•
the signature is wrong: 0800 0020
hex
Tip!
For module parameter storing, the signature “ save” must be in the telegram data.
Assignment of telegram data words for parameter storing
Signature
MSB
LSB
ISO 8859 (ASCII)
e
v
a
s
hex
65
76
61
73
Bit assignment for reading right
U32
0
1
2 - 31
0/1
0/1
0
0
0
..
0
0
0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com
Show/Hide Bookmarks