Technical Data
821XKlimaBA0399
3-3
120 % overload
8214
8213
8212
8211
Type
EVF8214-E-
V020
EVF8213-E-
V020
EVF8212-E-
V020
EVF8211-E-
V020
Order no.
Motor voltage
3)
V
M
[V]
0 - 3
V
mains
/ 0Hz
¡
50Hz, if required up to 480Hz
Power loss (Operation with I
Nx
)
P
v
[W]
65
75
100
100
Power derating
[%/K]
[%/m]
40
C < T
amb
< 50
C: 2.5%/K
1000 m a.m.s.l
h
$
4000 m a.m.s.l: 5%/1000m
Field
frequency
Resolution
absolute
0.02 Hz
Field
frequency
Digital setpoint
selection
Accuracy
á
0.05 Hz
Analog setpoint
selection
Linearity
á
0.5 % (max. selected signal level: 5 V or 10 V)
Analog setpoint
selection
Temperature
sensitivity
0
¡
40
C: + 0.4 %
Offset
á
0 %
Weight
m [kg]
2.2
2.2
2.2
2.2
1)
This power can be additionally obtained when operating a matching motor
2)
The currents applyto a periodical load cycle with 1 minute overcurrent with the current mentioned here
and 2 minutes base load with 75% I
Nx
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
*
No dynamic chopper-frequency lowering of the inverter
Show/Hide Bookmarks
Summary of Contents for 8210 HVAC Series
Page 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Page 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Page 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Page 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Page 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...