Technical Data
821XKlimaBA0399
3-5
3.3 Rated data
(Operation with 150 % overload)
Operation permitted with a mains voltage of
3AC / 400 V - 460V / 50/60 Hz
3.3.1
Types 8211 to 8214
150 % overload
Type
8211
8212
8213
8214
Mains voltage
V
rated
[V]
320V - 0%
$
V
rated
$
510V + 0%;
45Hz
¡
65Hz
á
0%
Alternative DC supply
V
DC
[V]
450 V - 0%
$
V
DC
$
715 V +
0%
Mains current
with mains filter/mains choke
without mains filter/mains choke
I
mains
[A]
I
mains
[A]
2.5
3.75
3.9
5.85
5.0
7.5
7.0
--
Data for mains operation with 3 AC/400 V/50 Hz/60 Hz; 450 V
$
V
DC
$
620 V or
3 AC/460 V/50 Hz/60 Hz; 460 V
$
V
DC
$
725 V
400V 460V 400V 460V 400V 460V 400V 460V
Motor power (4 pole ASM)
off 4kHz/8kHz*
P
rated
[kW]
0.75
1.1
1.5
1.5
2.2
2.2
3.0
3.7
Motor power (4 pole ASM)
off 4kHz/8kHz*
P
rated
[hp]
1.0
1.5
2.0
2.0
2.9
2.9
4.0
5.0
Output power U, V, W
off 4 kHz/8 kHz*
S
rated8
[kVA]
1.6
1.9
2.7
3.1
3.8
4.3
5.2
5.8
Output power + U
G
, -U
G
1)
P
DC
[kW]
0.7
0.7
0.0
0.0
1.0
1.0
0.0
0.0
4 kHz*
I
rated4
[A]
2.4
2.4
3.9
3.9
5.5
5.5
7.3
7.3
8 kHz*
I
rated8
[A]
2.4
2.4
3.9
3.9
5.5
5.5
7.3
7.3
12 kHz*
I
rated12
[A]
2.0
1.9
3.3
3.0
4.6
4.3
6.1
5.7
16 kHz*
I
rated16
[A]
1.8
1.7
2.9
2.7
4.1
3.8
5.5
5.1
noise optimized 4 kHz*
I
rated4
[A]
2.4
2.3
3.9
3.7
5.5
5.2
7.3
6.9
noise optimized 8 kHz*
I
rated8
[A]
2.1
2.0
3.4
3.2
4.7
4.5
6.3
6.0
noise optimized 12 kHz*
I
rated12
[A]
1.9
1.8
3.1
2.9
4.4
4.1
5.8
5.4
noise optimized 16 kHz*
I
rated16
[A]
1.6
1.5
2.5
2.3
3.6
3.3
4.7
4.4
Max.
output
4 kHz*
I
rated max4
[A]
3.6
3.6
5.9
5.9
8.3
8.3
11.0
11.0
Max.
output
current
8 kHz*
I
rated max8
[A]
3.6
3.6
5.9
5.9
8.3
8.3
11.0
11.0
current
for
60s
2)
12 kHz*
I
rated max12
[A]
3.0
2.8
4.9
4.6
6.9
6.6
9.2
8.7
for
60s
2)
16 kHz*
I
rated max16
[A]
2.7
2.5
4.4
4.1
6.2
5.8
8.2
7.7
noise optimized 4 kHz*
I
rated max4
[A]
3.6
3.7
5.9
5.6
8.3
7.8
11.0
10.4
noise optimized 8 kHz*
I
rated max8
[A]
3.1
2.9
5.1
4.8
7.1
6.7
9.4
8.9
noise optimized 12 kHz*
I
rated max12
[A]
2.9
2.7
4.7
4.4
6.6
6.2
8.8
8.2
noise optimized 16 kHz*
I
rated max16
[A]
2.4
2.1
3.8
3.5
5.4
5.0
7.1
6.6
Power loss (Operation with I
rated
)
P
v
[W]
55
75
90
100
*
No dynamic chopper-frequency lowering of the inverter
For all other data see chapter 3.2.2.
Show/Hide Bookmarks
Summary of Contents for 8210 HVAC Series
Page 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Page 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Page 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Page 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Page 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...