Commissioning
821XKlimaBA0399
5-1
5 Commissioning
The controllers are factory-set to drive a corresponding four-pole
standard asynchronous motor. Further settings are not necessary.
-
230/400 V, 50 Hz
-
265/460 V, 60 Hz
-
280/480 V, 60 Hz
Only a few settings via the 8201 BB operating module or a fieldbus
module are necessary to adapt your drive to your application. The
steps required are summarized in chapter 5.3 und in Kap. 5.4.
5.1 Before you switch on
Prior to initial switch-on of the controller, check the wiring for
completeness, short-circuit, and earth fault:
-
Power connection:
- Via L1, L2 and L3
- Alternatively via terUG, -UG (DC-group drive)
-
Control terminals:
- Reference potential for the control terminals is terminal 39.
- Controller enable: terminal 28
- Selection of direction of rotation: terminal E3 or E4
- External setpoint selection: terminals 8, 9
- Check jumper position! Factory setting: 0 - 10 V
(see the table in chapter 4.2.3.2).
- During operation with an internal voltage supply via
terminal 20, bride the terminals 7 and 39.
-
In case of condensation connect the controller to mains
voltage only after the visible humidity has evaporated.
Maintain the switch-on sequence!
Show/Hide Bookmarks
Summary of Contents for 8210 HVAC Series
Page 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Page 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Page 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Page 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Page 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...