Commissioning
821XKlimaBA0399
5-9
3.Set the Vmin boost
(C016).
-
Load independent boost of the motor voltage for field frequencies below the rated
V/f frequency. You can thus optimize the torque performance of the inverter drive.
-
It is absolutely necessary to adapt the asynchronous motor used, since otherwise,
the motor can be destroyed by overtemperatue:
Adjustment
Please note the thermal characteristic of the connected motor under small field
frequencies:
-
Usually, standard asynchronous motos with the insulation class B can be driven for
a short time with rated current in the frequency range 0Hz
$
f
d
$
25Hz.
-
Please ask the motor manufacturer for the exact setting values for the motor
current.
A Operate the motor when no load is applied with a slip frequency of f
d
:
- P
mot
$
7.5 kW: f
d
5 Hz
- P
Mot
7,5 kW: f
d
2 Hz
B Increase V
min
until you reach the following motor current:
- Motor in short-term operation at 0Hz
$
f
d
$
25Hz:
with self-ventilated motors:
I
motor
$
I
rated motor
with forced-ventilated motors:
I
motor
$
I
rated motor
- Motor in permanent operation at 0Hz
$
f
d
$
25Hz:
with self-ventilated motors
I
motor
$
0.8
k
I
rated motor
with forced ventilated motors:
I
motor
$
I
rated motor
4.Set slip compensation
(C021).
Rough setting by means of the motor data:
4.Set slip compensation
(C021).
s
n
rsyn
n
r
n
rsyn
ô
100%
n
rsyn
f
dr
ô
60
p
s
Slip constant (C021)
n
rsyn
synchronous motor speed [min
-1
]
n
r
rated speed to motor nameplate [min
-1
]
f
dr
rated frequency to motor nameplate [Hz]
p
Number of pole pairs
Precise setting:
Change C021 under constant load until the speed is near the synchronous speed.
If C021 is set to too high values, the drive may become instable (overcompensation).
Important
The change from V/f-characteristic control to motor-current control should only be
made when the controller is inhibited.
Show/Hide Bookmarks
Summary of Contents for 8210 HVAC Series
Page 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Page 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Page 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Page 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Page 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...