Configuration
7-10
821XKlimaBA0399
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C114
¤
Signal level
digital inputs
-0-
E4
E3
E2
E1
-0-
0
0
0
0
-1-
0
0
0
1
-2-
0
0
1
0
-3-
0
0
1
1
-4-
0
1
0
0
-5-
0
1
0
1
-6-
0
1
1
0
-7-
0
1
1
1
-8-
1
0
0
0
-9-
1
0
0
1
-10-
1
0
1
0
-11-
1
0
1
1
-12-
1
1
0
0
-13-
1
1
0
1
-14-
1
1
1
0
-15-
1
1
1
1
0: Ex is not
inverted
1: Ex is inverted
C115
¤
Priority mask
digital inputs
-0-
E4
E3
E2
E1
-0-
0
0
0
0
-1-
0
0
0
1
-2-
0
0
1
0
-3-
0
0
1
1
-4-
0
1
0
0
-5-
0
1
0
1
-6-
0
1
1
0
-7-
0
1
1
1
-8-
1
0
0
0
-9-
1
0
0
1
-10-
1
0
1
0
-11-
1
0
1
1
-12-
1
1
0
0
-13-
1
1
0
1
-14-
1
1
1
0
-15-
1
1
1
1
0: Function Ex
depends on C001
1: Function Ex is
independent of
C001
-
Ctrl. inhibit and
TRIP reset
always have
first priority.
-
With -0- also
TRIP set and
QSP have
priority.
C119
¤
Function PTC
822X/824X
-0-
-0-
PTC input not active
-1-
PTC input active, TRIP and pulse inhibit will
be set
-2-
PTC input active, warning
C120 I
2
k
t switch off
822X/824X
0
0
{1 %}
100
C125
¤
*
LECOM baud rate
-0-
-0-
9600 baud
-1-
4800 baud
-2-
2400 baud
-3-
1200 baud
-4-
19200 baud
Only for LECOM
applications
Show/Hide Bookmarks
Summary of Contents for 8210 HVAC Series
Page 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Page 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Page 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Page 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Page 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...