Configuration
821XKlimaBA0399
7-13
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Selection
Lenze
Name
C427* Offset adjustment
frequency input
E1
0.0
-12.5
{0.1 %}
12.5
C500* Display factor
application datum
2000
1
{1}
25000
application datum
numerator
C501* Display factor for
process variable
10
1
{1}
25000
process variable
denominator
C597*
¤
Activation of
motor-phase
failure detection
822X/824X
-0-
-0-
Inactive
-1-
TRIP
-2-
Warning
C599* Current limit
value
motor-phase
failure detection
822X/824X
5
1
{1 %}
50
C625* Frequency 1
480.00 0.00
{0.02 Hz}
480.00
C626* Frequency 2
480.00 0.00
{0.02 Hz}
480.00
C627* Frequency 3
480.00 0.00
{0.02 Hz}
480.00
C628* Bandwidth of
frequencies
0.00
0.00
{0.01 %}
100.00
C988* DC-bus voltage
threshold for
DC-bus voltage
control
0
0
{1 %}
200
-
C988 = 0%
- No
parameter
set
changeover
via DC-bus
voltage
-
C988 = 1 ...
200%
- Parameter
set
changeover
via DC-bus
voltage
active
Parameter set
changeover via
terminal or
LECOM is not
possible when
C988 > 0!
Show/Hide Bookmarks
Summary of Contents for 8210 HVAC Series
Page 52: ...Commissioning 5 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 62: ...Commissioning 5 24 821XKlimaBA0399 Show Hide Bookmarks...
Page 64: ...During operation 6 2 821XKlimaBA0399 Show Hide Bookmarks...
Page 78: ...Configuration 7 14 821XKlimaBA0399 Show Hide Bookmarks...
Page 84: ...Troubleshooting and fault elimination 8 6 821XKlimaBA0399 Show Hide Bookmarks...
Page 88: ...Accessories 9 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 92: ...Index 10 4 821XKlimaBA0399 Show Hide Bookmarks...
Page 93: ...Index 821XKlimaBA0399 10 5 Show Hide Bookmarks...
Page 94: ...Index 10 6 821XKlimaBA0399 Show Hide Bookmarks...