Commissioning
Before switching on
7
l
141
EDS84ASC552 EN 6.0
7
Commissioning
)
Note!
Please observe:
ƒ
the general safety instructions (
¶
ƒ
the residual hazards (
¶
7.1
Before switching on
)
Note!
ƒ
Comply with the corresponding switch−on sequence.
ƒ
In case of faults during commissioning please use:
– the chapter "Diagnostics"
– the online help in the »Engineer«
– the 8400 StateLine C or 8400 HighLine C software manual
To prevent injury to persons or damage to material assets, check ...
... before connecting the mains voltage:
ƒ
Wiring for completeness, short circuit, and earth fault
ƒ
The "EMERGENCY STOP" function of the entire system
ƒ
The motor circuit configuration (star/delta) must be adapted to the output voltage
of the controller
ƒ
The in−phase connection of the motor
ƒ
The direction of rotation or the incremental encoder (if available)
... the most important drive parameter settings before the controller is enabled:
ƒ
Is the V/f rated frequency adapted to the motor circuit configuration?
ƒ
Are the drive parameters relevant for your application set correctly?
ƒ
Is the configuration of the analog and digital inputs and outputs adapted to wiring?