Product description
Overview of control terminals
l
20
EDS84ASC552 EN 6.0
3.3
Overview of control terminals
Control terminals for devices in the StateLine version
Control terminals for devices in the HighLine version
8400HLC080a
8400HLC081a
Connection
Information
Pos.
Description
StateLine C
HighLine C
X1
CANopen connection
^
S1
CANopen settings
X3
analog inputs/outputs; 10V reference voltage
^
^
X4
Digital inputs; controller enable
^
−
24V supply of the control electronics
Digital outputs
^
24V voltage output
X5
Digital inputs; controller enable
−
^
External 24V supply of the control electronics; internal 24V supply
fused via PTC
X6 (DIAG)
Diagnostic interface
^
x107
24 V brake supply;
−
^
+ BD1
Connection for DC brake coil
− BD2
MMI
Slot for memory module (Memory Module Interface)
^
2
Icon
Description
{
Long discharge time
: All power terminals remain live for a few minutes after mains
disconnection! The duration is given under the warning symbol on the device.
}
High discharge current
: Carry out fixed installation and PE connection according to
EN 61800−5−1!
'
Electrostatic sensitive devices
: Before working on the device, the personnel must be free of
electrostatic charge!
|
Hot surface
: Risk of burns! Hot surfaces should not be touched without wearing protective
gloves.