Technical data
Rated data
Overview
l
27
EDS84ASC552 EN 6.0
4.2
Rated data
4.2.1
Overview
Input data
Basis of the data
Mains
Voltage
U
LN
[V]
Voltage range
U
LN
[V]
Frequency range
f [Hz]
1/N/PE AC
230
180 − 0 % ... 264 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
400
320 − 0 % ... 440 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
500
400 − 0 % ... 550 + 0 %
45 − 0 % ... 65 + 0 %
Voltage
Frequency
Current [A]
Number of
phases
Type
[V]
[Hz]
max. +45 °C
max. +55 °C
E84AVxxx2512
230
50/60
3.4
2.6
1
E84AVxxx3712
230
50/60
5.0
3.8
1
E84AVxxx5512
230
50/60
5.3
4.0
1
E84AVxxx7512
230
50/60
8.0
6.0
1
E84AVxxx1122
230
50/60
12.0
9.0
1
E84AVxxx1522
230
50/60
13.7
10.3
1
E84AVxxx2222
230
50/60
21.8
16.3
1
E84AVxxx3714
400/500
50/60
1.8/1.4
1.4/1.1
3
E84AVxxx5514
400/500
50/60
2.7/2.2
2.0/1.7
3
E84AVxxx7514
400/500
50/60
3.6/2.9
2.7/2.2
3
E84AVxxx1124
400/500
50/60
4.4/3.6
3.3/2.7
3
E84AVxxx1524
400/500
50/60
5.5/4.4
4.1/3.3
3
E84AVxxx2224
400/500
50/60
7.3/5.8
5.5/4.4
3
E84AVxxx3024
400/500
50/60
9.8/7.8
7.35/5.8
3
E84AVxxx4024
400/500
50/60
13.1/10.5
9.8/7.8
3
E84AVxxx5524
400/500
50/60
18/14.4
13.5/10.8
3
E84AVxxx7524
400/500
50/60
20.0/16.0
15.0/12.0
3
E84AVxxx1134
400/500
50/60
29.0/23.2
21.7/17.4
3
E84AVxxx1534
400/500
50/60
29.0
2)
/23.2
2)
21.4
2)
/17.4
2)
3
E84AVxxx1834
400/500
50/60
36.0
2)
/31.0
2)
27.0
2)
/23.3
2)
3
E84AVxxx2234
400/500
50/60
43.0
2)
/37.0
2)
32.3
2)
/27.8
2)
3
Ambient temperature in the control cabinet, switching frequency 2 and 4 kHz, operation without mains choke
2)
only with mains choke