Technical data
Rated data
Operation at rated mains voltage 400 V
l
39
EDS84ASC552 EN 6.0
Operation with external mains choke/mains filter
Type
Installation according to EN 60204−1
1)
Installation according
to UL
2)
FI
3)
L1, L2, L3 − Laying system
L1, L2, L3
B2
C
F
[A]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
[AWG]
[mA]
E84AVxxx3714
C 6
6
1.0
−
−
6
18
E84AVxxx5514
C 6
6
1.0
−
−
6
18
30
3)
E84AVxxx7514
C 6
6
1.0
−
−
6
18
E84AVxxx1124
C 6
6
1.0
−
−
10
16
30
3)
E84AVxxx1524
C 6
6
1.0
−
−
10
16
E84AVxxx2224
C 10
10
1.5
−
−
10
16
E84AVxxx3024
C 10
10
1.5
−
−
15
14
300
3)
E84AVxxx4024
C 16
16
2.5
−
−
20
12
E84AVxxx5524
C 20
20
4
−
−
20
12
E84AVxxx7524
C 20
20
4
−
−
20
12
300
3)
E84AVxxx1134
C 32
32
10
−
−
30
10
E84AVxxx1534
C 32
32
10
−
−
40
8
E84AVxxx1834
C 50
50
16
−
−
−
−
300
3)
E84AVxxx2234
C 63
63
25
−
−
−
−
1)
These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to
VDE 0298−4). The cable cross−sections apply under the following conditions: Use of PVC−insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Use UL−approved cables, fuses and fuse holders only.
UL fuse: voltage
500 V, tripping characteristic for example "H", "K5" or "CC". The cable cross−sections apply under
the following conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal−current sensitive earth−leakage circuit breaker, short−time delay
If cables are longer than 50 m, the protective circuit−breaker may respond, depending on the cable type and
switching frequency.
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations
efesotomasyon.com - Lenze