Mechanical installation
Standard devices in the power range 0.25 ... 2.2 kW
Mounting in "cold plate" technique
l
69
EDS84ASC552 EN 6.0
5.2.3
Mounting in "cold plate" technique
The E84AVxx
C
... controllers are designed for assembly on coolers (e.g. collective coolers) in
"cold−plate" technique.
Requirements for collective coolers
The following items are important for the safe operation of the drive controllers:
ƒ
Good thermal connection to the cooler
– The contact area between the collective cooler and the drive controller must be at
least as big as the cooling plate of the drive controller.
– Even contact area, max. deviation 0.05mm.
– Connect the collective cooler with the drive controller with all the required
screwed joints.
ƒ
Observe the thermal resistance R
th
according to the table. The data includes the heat
transmission between the cooler and the device. With a standard heat conducting
paste and a film thickness of 50
m, it is approx. 0.03K/W. The values apply for the
operation of the drive controllers under rated conditions.
Power to be dissipated
Heatsink environment
Type
P
v [W]
R
th
[K/W]
E84AVxxC2512
15
1.5
E84AVxxC3712
20
1.5
E84AVxxC5512
30
1.0
E84AVxxC7512
40
1.0
E84AVxxC1122
60
0.6
E84AVxxC1522
75
0.5
E84AVxxC2222
100
0.4
E84AVxxC3714
25
1.0
E84AVxxC5514
35
1.0
E84AVxxC7514
50
1.0
E84AVxxC1124
60
0.6
E84AVxxC1524
70
0.5
E84AVxxC2224
100
0.4