Mechanical installation
Standard devices in the power range 3 ... 22 kW
Mounting in "cold plate" technique
l
79
EDS84ASC552 EN 6.0
5.3.3
Mounting in "cold plate" technique
The E84AVxx
C
... controllers are designed for assembly on coolers (e.g. collective coolers) in
"cold−plate" technique.
Requirements for collective coolers
The following items are important for the safe operation of the drive controllers:
ƒ
Good thermal connection to the cooler
– The contact area between the collective cooler and the drive controller must be at
least as big as the cooling plate of the drive controller.
– Even contact area, max. deviation 0.05mm.
– Connect the collective cooler with the drive controller with all the required
screwed joints.
ƒ
Observe the thermal resistance R
th
according to the table. The data includes the heat
transmission between the cooler and the device. With a standard heat conducting
paste and a film thickness of 50
m, it is approx. 0.03K/W. The values apply for the
operation of the drive controllers under rated conditions.
Power to be dissipated
Heatsink environment
Type
P
v [W]
R
th
[K/W]
E84AVxxC3024
115
0.33
E84AVxxC4024
155
0.25
E84AVxxC5524
215
0.18
E84AVxxC7524
250
0.15
E84AVxxC1134
355
0.11
E84AVxxC1534
390
0.10