Electrical installation
Devices in the power range 0.25 ... 2.2 kW (1/N/PE AC 230 V)
Terminal assignment of the power connections
l
108
EDS84ASC552 EN 6.0
Motor temperature monitoring
)
Note!
In the Lenze setting, motor temperature monitoring is activated! In the
delivery status, there is a wire jumper between the terminals X106/T1 and
X106/T2. Before connecting a thermal sensor, remove the wire jumper.
)
Note!
– If the terminal X106 is used, e.g. to connect an external PTC thermistor or
a thermal contact, ensure at least one basic insulation to the motor or
mains potential to not restrict the protective separation of the control
terminals.
– The terminal X106 is connected to PE inside the device but cannot be used
for protective earth.
Terminal X106
Labelling
Description
T1
T2
Motor temperature monitoring with PTC element
(type−A sensor, switching performance acc. to EN 60947−8 for
type−A tripping units) or thermostat
(NC contact).
Lenze setting: activated, error message
Setting in C00585
8400GG016b
Terminal data
Conductor cross−section
Tightening torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
E84AVxxx2512
E84AVxxx3712
E84AVxxx5512
E84AVxxx7512
E84AVxxx1122
E84AVxxx1522
E84AVxxx2222
0.2 ... 1.5
24 ... 16
−
−
2.5 x 0.4
I
Tip!
For an easy removal of the wire jumper:
1. Cut the wire jumper with side−cutting pliers.
2. Overcome the spring pressure of the terminal with a screwdriver.
3. Remove both wire ends individually.