Technical data
StateLine C control terminals
Digital inputs
l
56
EDS84ASC552 EN 6.0
4.6.4
Digital inputs
Labelling
Features
Rated value
X4/DI1, DI2
Digital input 1/2
In accordance with IEC61131−2, type 1
or
two−track frequency input for HTL
encoder 0 ... 10 kHz
X4/DI3, DI4
Digital input 3/4
In accordance with IEC61131−2, type 1
X4/RFR
Controller inhibit
In accordance with IEC61131−2, type 1
Input resistance
3.3 k
(2.5 k
... 6 k
)
Electric strength of external voltage
Up to
±30 V, permanent
Isolation
^
Level
LOW < +5V
HIGH > +15V
Cycle time
1 ms, can be changed by software
filtering
X4/GIO
GND, reference potential for digital signals
4.6.5
Digital outputs
Labelling
Features
Rated value
X4/DO1
Digital output
In accordance with IEC61131−2, type 1, max.
50 mA
External−voltage protected
Up to +30 V
Integrated polarity reversal protection diode
for switching inductive loads
Isolation
^
Level
LOW < +5 V
High > +15 V
Time−dependent behaviour
LOW − HIGH / HIGH − LOW
Max. 250
s
Overload behaviour
Reduced voltage or periodical switch−off/on
Reset and switch−on behaviour
Outputs are switched off (LOW)
Cycle time
1 ms
X4/GIO
GND, reference potential for digital signals
4.6.6
Relay output connection
Labelling
Description/features
Rated value
X101
COM
Central contact of relay
AC 250 V, 3 A
DC 24V, 2A
DC 240 V, 0.16 A
According to UL508C:
– 3 A, 250 V AC (general purpose)
– 2 A, 24 V DC (resistive)
– 0.16 A, 240 V DC (general purpose)
NC
COM
NC contact (normally closed)
Position is displayed via TRIP software
message
(Lenze setting)
NO
COM
NO contact (normally open)
efesotomasyon.com - Lenze