How to carry out automatic motor parameter identification:
1. Inhibit the controller if it is enabled, e.g. via the
C00002/16
device command or a
LOW signal at the X4/RFR terminal.
• For executing the motor parameter identification, the controller must be in the
"
SwitchedOn
" status.
2. Wait until the drive is at standstill.
3. Ensure that a motor control suitable for the motor is set in
C00006
.
4. Transfer the nameplate data to the following codes:
•
C00081
: Rated motor power
•
C00087
: Rated motor speed
•
C00088
: Rated motor current (according to the connection method
/
)
•
C00089
: Rated motor frequency (according to the connection method
/
)
•
C00090
: Rated motor voltage (according to the connection method
/
)
•
C00091
: Motor cos
ϕ
5. Defining the motor cable length and motor cable cross-section:
•
C00915
: Motor cable length
•
C00916
: Motor cable cross-section
The resulting motor cable resistance is displayed in
C00917
.
6. Activate motor parameter identification via the
C00002/23
= "1: On / start" device
command.
7. Enable the controller again.
• The controller changes to the "
MotorIdent
" device status.
• Motor parameter identification starts.
• The progress of the identification run can be seen in
C00002/23
.
• The identification is completed if the "0: Off / ready" message is displayed in
C00002/23
.
• After successful identification, it changes back to the "
SwitchedOn
" device
status.
8. Inhibit controller again.