8400 StateLine C | Reference manual
Motor control (MCTRL)
Parameterisable additional functions
216
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
Example: Voltage increase in the DC bus when field weakening is switched off
(For instance by an active setting of the controller inhibit or by tripping a fault or error at
high motor speed.)
[5-24] Example: Possible DC-bus voltage > 800 V if field weakening gets lost
Field weakening
Speed n
Motor voltage peak value
Switched off
4000 rpm
560 V
5700 rpm
800 V
6000 rpm
840 V
Switched-on
6000 rpm
560 V
If pulse inhibit occurs at 6000 rpm and switched-on
field weakening, the DC bus is loaded to more than
800 V (
n
).
A speed limitation to 5700 rpm is required since this
speed causes a DC-bus voltage of 800 V if field
weakening is switched off.
n
U
4000
840 V
560 V
6000
> 800 V