8400 StateLine C | Reference manual
Technology applications
TA "Switch-off positioning"
326
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
wStateDetermFailNoHigh
WORD
Display of the status determining error (HIGH word)
bDriveFail
BOOL
TRUE Drive controller in error status.
• "
Fault
" device status is active.
bWarningActive
BOOL
TRUE A monitoring in the drive controller, for which the error response
"Warning" or "Warning locked" has been parameterised, responded.
• "
Warning
" device status is active.
bSafeTorqueOff
BOOL
TRUE Safe torque off.
• "
SafeTorqueOff
" device status is active.
bDriveReady
BOOL
TRUE Controller is ready for operation.
• "
SwitchedOn
" device status is active.
• The drive is in this device status if the DC bus voltage is applied
and the controller is still inhibited by the user (controller inhibit).
bCInhActive
BOOL
TRUE Controller inhibit is active.
bImpIsActive
BOOL
TRUE Pulse inhibit is active.
bQSPIsActive
BOOL
TRUE Quick stop is active.
bSpeedCcw
BOOL
Current direction of rotation
FALSE Direction of rotation to the right (Cw)
TRUE Direction of rotation to the left (Ccw)
bSpeedActCompare
BOOL
Result of the speed comparison
TRUE During open-loop operation:
Speed setpoint < Comparison value (
C00024
)
During closed-loop operation:
Actual speed value < Comparison value (
C00024
)
bImaxActive
BOOL
"Current setpoint inside the limitation" status signal
TRUE The current setpoint is internally limited (the drive controller
operates at the maximum current limit).
bSpeedSetReached
BOOL
Status signal "setpoint = 0"
TRUE Speed setpoint from the ramp function generator = 0
bSpeedActEqSet
BOOL
TRUE Actual speed value = speed setpoint
nMotorCurrent_a
INT
Current stator current/effective motor current
• Scaling: 16384
≡
100 % I
max_mot
(
C00022
)
nMotorSpeedSet_a
INT
Speed setpoint
• Scaling: 16384
≡
100 % reference speed (
C00011
)
nMotorSpeedAct_a
INT
Actual speed value
• Scaling: 16384
≡
100 % reference speed (
C00011
)
nMotorTorqueAct_a
INT
Actual torque
• In the "VFC (+encoder)" operating mode of the motor control, this value is
determined from the current motor current and corresponds to the actual torque
only by approximation.
• Scaling: 16384
≡
100 % M
max
(
C00057
)
nDCVoltage_a
INT
Actual DC-bus voltage
• Scaling: 16384
≡
1000 V
nMotorVoltage_a
INT
Current motor voltage/inverter output voltage
• Scaling: 16384
≡
1000 V
Identifier
Data type
Value/meaning