8400 StateLine C | Reference manual
Technology applications
TA "Switch-off positioning"
336
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
7.3.3.7
CAN
Process data assignment for fieldbus communication
(
338)
Connection
Assignment
Connection
Assignment
X101/NC-NO
LA_SwitchPos.bDriveFail
X4/RFR
LA_SwitchPos: bFailReset
X3/A1U
LA_SwitchPos.nAuxSetValue_a *
X4/DI1
LA_SwitchPos: bJogCtrlStop1
X3/A1I
-
X4/DI2
LA_SwitchPos: bJogCtrlSlowDown1
X3/O1U
-
X4/DI3
LA_SwitchPos: bJogCtrlStop2
* 10 V
≡
100 % reference speed (
C00011
)
X4/DI4
LA_SwitchPos: bJogCtrlSlowDown2
X4/DO1
LA_SwitchPos.bDriveReady
Note!
You must set the setpoint arithmetic in
C00190
to "1: NOut = NSet + NAdd" so
that the additional speed setpoint selected via the analog input A1U has an
additive effect.
+
=
+
+
X4
DI3
DI2
DI4
GIO
24I
DI1
RFR
24E
+
X3
AR
A1U
GA
A1I
DO1
O1U
-
COM
NC
NO
X101
LP_CanIn1
LP_CanOut1
wCtrl
wIn2
wIn3
DriveControl
MainSetValue
-
wState
wOut2
wOut3
DriveControlStatus
MotorSpeedAct
GPSignalOut1
wOut4 -
CG
C
L
CH
X1
Stop function 2
Stop function 1
Selection of pre-switch off 1
Selection of pre-switch off 2
External
supply
24 V DC
Additional speed setpoint
Controller enable / reset error
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com