Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
409
8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
9.9.6
Cause & possible remedies
This chapter contains all error messages of the controller operating system in numerical
order of the error numbers. The list provides detailed information on the response to the
error message as well as information on the cause & possible remedies.
Tip!
A list of all error messages of the controller operating system in alphabetical order
can be found in the previous chapter "
Short overview (A-Z)
"
(
407)
.
Su02: One mains phase is missing [xx.0111.00002]
Su03: Too frequent mains switching [xx.0111.00003]
Su04: CU insufficiently supplied [xx.0111.00004]
Note!
For the sake of legibility, the
Logbook
and
C00165
display the error number with
the following syntax:
[
Error type
]
.
[
Error subject area no.
]
.
[
Error ID
]
In this documentation, "xx", a wildcard, stands for the error type since it is
configurable for many error messages.
Response
(Lenze setting printed in bold)
Setting:
C00565
(
;
Adjustable response)
;
0: No Reaction
;
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
:
5: Warning
6: Information
Cause
Remedy
One mains phase of a three-phase supply has failed.
Check mains connection (terminal X100).
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Too frequent mains switching of the power section.
• The device recognises if the power section is switched
on and off too frequently.
• To protect internal charging connections from
destruction, the device reports this error and prevents
the controller inhibit. All other functions are active.
The error must be acknowledged by mains switching.
The charging circuit can only cool down when the mains
is switched off.
• After switching the mains 3 times in one minute,
there must be a switching pause of 9 minutes.
• Cyclic mains switching every 3 minutes is permissible.
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
After switching on the device, the 24V supply voltage for
the control electronics is too low (100ms after switch-on
U is < 19V).
• The current supply voltage is displayed in
C00065
.
The error must be acknowledged.
With internal supply voltage via the power electronics,
the controller must be replaced.
With external supply voltage, check the correct
connection and/or the stability of the supply voltage.