8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
410
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
Su06: Mains input overload [xx.0111.00006]
oH4: Heatsink temp. > shutdown temp. -5°C [xx.0119.00000]
oH1: Overtemperature heatsink [xx.0119.00001]
oH3: Motor temperature (X106) triggered [xx.0119.00015]
oC5: Ixt overload [xx.0119.00050]
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Overtemperature in case of devices from type 6 in the
input rectifier or the mains choke.
• Check whether all mains phases are connected (a 2-
phase supply may be existent).
• Provide for sufficient cooling of the device.
Response
(Lenze setting printed in bold)
Setting:
C00582
(
;
Adjustable response)
:
0: No Reaction
;
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
;
5: Warning
6: Information
Cause
Remedy
The heatsink temperature now only differs by 5 °C from
the shutdown temperature of the motor.
Prevent further heating, i.e. reduce motor load or set
controller inhibit so that the heatsink can cool down
again.
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The heatsink temperature is higher than the fixed limit
temperature (90 ° C).
Maybe the ambient temperature of the controller is too
high or the fan or its ventilation slots are dirty.
• Check control cabinet temperature.
• Clean filter.
• Clean controller.
• If required, clean or replace the fan.
• Provide for sufficient cooling of the device.
Response
(Lenze setting printed in bold)
Setting:
C00585
(
;
Adjustable response)
;
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
;
5: Warning
6: Information
Cause
Remedy
The motor temperature monitoring function at the plug
connector X106, terminal T1 /T2, has tripped.
Possible causes:
• The motor is overheated so that the thermal contact
integrated into the motor has been switched.
• An open circuit or a loose contact at the connections
mentioned above has occurred.
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.
Response
(Lenze setting printed in bold)
Setting:
C00604
(
;
Adjustable response)
;
0: No Reaction
;
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
:
5: Warning
6: Information
Cause
Remedy
The Ixt overload check has tripped.
• Operating threshold = 100 % Ixt (adjustable in
C00123
)
Possible causes:
• Wrong dimensioning of the device with regard to its
motor load.
• Load cycles are not complied with.
• Check and, if required, correct dimensioning of the
device and the motor load with regard to technical
data.
• Reduce motor load cycles (observe load cycles
according to documentation).