8400 StateLine C | Reference manual
Diagnostics & error management
Error messages of the operating system
PS09: Par. format invalid [xx.0144.00009]
PS10: Memory module binding invalid [xx.0144.00010]
dF14: SW-HW invalid [xx.0145.00014]
dF18: BU RCOM error [xx.0145.00024]
dF25: CU RCOM error [xx.0145.00025]
dF26: Appl. watchdog [xx.0145.00026]
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
The code format is invalid.
• The error occurs while loading the parameter set.
Consultation with Lenze required.
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Active device personalisation: The memory module and
the controller do not have identical binding IDs.
• Use memory modules/controllers with matching
binding IDs.
• Consult the machine manufacturer.
Note:
Lenze cannot modify e.g. a replacement device via
special access to make it work with a personalised
memory module.
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response
(Lenze setting printed in bold)
0: No Reaction
:
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
5: Warning
6: Information
Cause
Remedy
Mains switching too frequent.
• Cyclic mains switching every 3 minutes is permissible.
• After switching the mains 3 times in one minute,
there must be a switching pause of 9 minutes.
• If the problem occurs again, you needs to consult
Lenze.
Response
(Lenze setting printed in bold)
Setting:
C00580/1
(
;
Adjustable response)
:
0: No Reaction
;
1: Fault
2: Trouble
3: TroubleQuickStop
4: WarningLocked
;
5: Warning
6: Information
Cause
Remedy
Time-out of the application. The required computing
time of the application exceeds the available computing
time.
Reduction of the function block interconnection or the
complexity of the application.