8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00021
534
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00021
C00022
C00023
C00024
C00026
Parameter | Name:
C00021 | Slip comp.
Data type: INTEGER_16
Index: 24554
d
= 5FEA
h
Slip compensation for V/f characteristic control (
VFCplus
) and sensorless vector control (
SLVC
)
• A higher slip compensation results in a higher increase in frequency and voltage when the machine is under load.
• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered
automatically. An automatic detection via the motor parameter identification is possible as well.
Motor control (MCTRL)
:
Optimising the operational performance by slip compensation
Setting range
(min. value | unit | max. value)
Lenze setting
-100.00
%
100.00
2.67 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00022 | Imax in motor mode
Data type: UNSIGNED_16
Index: 24553
d
= 5FE9
h
Maximum current in motor mode for all motor control modes
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
A
655.35
47.00 A
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00023 | Imax in generator mode
Data type: INTEGER_16
Index: 24552
d
= 5FE8
h
Maximum current in generator mode for all motor control modes
• 100 %
≡
Imax in motor mode (
C00022
)
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
100.00
100.00 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00024 | LS_DriveInterface: bNActCompare
Data type: INTEGER_16
Index: 24551
d
= 5FE7
h
Threshold for the actual speed comparison
• This parameter serves to set a threshold that is compared with the actual speed value.
• If the value falls below this threshold, the
bNactCompare
output sets the
LS_DriveInterface
system block to
TRUE.
• Switching hysteresis = +1 %
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
199.99
0.00 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00026 | AINx: Offset
Data type: INTEGER_16
Index: 24549
d
= 5FE5
h
Offset for analog input
Analog terminals
Setting range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Lenze setting
Info
C00026/1
0.00 %
AIN1: Offset
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100