8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00103
546
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00103
C00105
C00106
C00107
Parameter | Name:
C00103 | Add. decel. time x
Data type: UNSIGNED_32
Index: 24472
d
= 5F98
h
The
L_NSet_1
FB: Additional deceleration times for the main setpoint
• The additional deceleration times set here can be selected via the binary inputs
bTI1
...
bTI8
of the
L_NSet_1
FB.
Setting range
(min. value | unit | max. value)
0.000
s
999.999
Subcodes
Lenze setting
Info
C00103/1
0.000 s
Add. decel. time 1 ... 15
C00103/...
C00103/15
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00105 | Decel. time - quick stop
Data type: UNSIGNED_32
Index: 24470
d
= 5F96
h
The set deceleration time determines the ramp slope at quick stop
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.900
2.000 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00106 | Auto DCB: Hold time
Data type: UNSIGNED_32
Index: 24469
d
= 5F95
h
Hold time of the automatic DC injection brake
• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in
C00019
.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.000
0.500 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00107 | DC braking: Hold time
Data type: UNSIGNED_32
Index: 24468
d
= 5F94
h
Maximum hold time of the manual DC injection brake
• A time can be set here after which the DC injection brake is switched off automatically to prevent the motor from
thermal overload.
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.000
999.000 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000