8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00169
C00169
C00170
C00171
C00173
Parameter | Name:
C00169 | Logbook setting
Data type: UNSIGNED_16
Index: 24406
d
= 5F56
h
Configuration which message types are to be logged in the logbook.
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF
0x067E
(decimal: 1662)
Value is bit-coded: (
;
= bit set)
Bit 0
Reserved
Bit 1
;
Log entry: Fault
Bit 2
;
Log entry: Trouble
Bit 3
;
Log entry: TroubleQuickstop
Bit 4
;
Log entry: WarningLocked
Bit 5
;
Log entry: Warning
Bit 6
;
Log entry: Information
Bit 7
Reserved
Bit 8
Reserved
Bit 9
;
Activation: Error counter
Bit 10
;
Activation: Log line refresh
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Parameter | Name:
C00170 | Current error
Data type: UNSIGNED_32
Index: 24405
d
= 5F55
h
Display of the internal error number of the currently pending error
Display range
(min. value | unit | max. value)
0
4294967295
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00171 | Logbook access index
Data type: UNSIGNED_8
Index: 24404
d
= 5F54
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00173 | Mains voltage
Data type: UNSIGNED_8
Index: 24402
d
= 5F52
h
If the rated mains voltage differs from 230 V or 400 V, set the mains voltage the drive is operated with.
The set mains voltage influences the brake chopper threshold, the monitoring of the device utilisation (Ixt) and the
switch-off threshold in case of undervoltage in the DC bus.
Selection list
(Lenze setting printed in bold)
Info
0 3ph 400V / 1ph 230V
3-phase 400 V or 1-phase 230 V
1 3ph 440V / 1ph 230V
3-phase 440 V or 1-phase 230 V
2 3ph 480V / 1ph 230V
3-phase 480 V or 1-phase 230 V
3 3ph 500V / 1ph 230V
3-phase 500 V or 1-phase 230 V
4 3ph 400V / 1ph 115V
3-phase 400 V or 1-phase 115 V
;
Read access
;
Write access
;
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1