Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
595
8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00423
C00423
C00425
C00434
Parameter | Name:
C00423 | DOx: Delay times
Data type: UNSIGNED_16
Index: 24152
d
= 5E58
h
Delay times for the digital output terminals
Digital terminals
Setting range
(min. value | unit | max. value)
0.000
s
65.000
Subcodes
Lenze setting
Info
C00423/1
0.000 s
Relay ON delay
C00423/2
0.000 s
Relay OFF delay
C00423/3
0.000 s
DO1 ON delay
C00423/4
0.000 s
DO1 OFF delay
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1000
Parameter | Name:
C00425 | Encoder scanning time
Data type: UNSIGNED_8
Index: 24150
d
= 5E56
h
From version 03.00.00
Encoder sample time for the digital input terminals when configured as frequency inputs
Using DI1 and DI2 as frequency inputs
Selection list
0 1 ms
1 2 ms
2 5 ms
3 10 ms
4 20 ms
5 50 ms
6 100 ms
7 200 ms
8 500 ms
9 1000 ms
Subcodes
Lenze setting
Info
C00425/1
3: 10 ms
FreqIn12: Encoder scanning time
;
Read access
;
Write access
;
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00434 | O1U gain
Data type: INTEGER_16
Index: 24141
d
= 5E4D
h
Gain of analog output
Analog terminals
Setting range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Lenze setting
Info
C00434/1
100.00 %
O1U: Gain
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100