8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00560
612
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00560
C00561
C00565
C00566
Parameter | Name:
C00560 | Fan switching status
Data type: UNSIGNED_8
Index: 24015
d
= 5DCF
h
From version 02.00.00
Display of the function status of the device fans
Selection list
0 Off
1 On
2 No fan
Subcodes
Info
C00560/1
Switching status - internal fan
C00560/2
Switching status - heatsink fan
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00561 | Failure indication
Data type: UNSIGNED_8
Index: 24014
d
= 5DCE
h
From version 02.00.00
Failure display of device fans and motor phases
Selection list
0 No error
1 Error
Subcodes
Info
C00561/1
Internal fan
C00561/2
Heatsink fan
C00561/3
Motor phase U
•
From version 11.00.00
C00561/4
Motor phase V
•
From version 11.00.00
C00561/5
Motor phase W
•
From version 11.00.00
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00565 | Resp. to mains phase failure
Data type: UNSIGNED_8
Index: 24010
d
= 5DCA
h
Response to the failure of mains phases
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00566 | Resp. to fan failure
Data type: UNSIGNED_8
Index: 24009
d
= 5DC9
h
Response to the detection of a fan failure
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1