8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00588
616
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00588
C00590
C00592
Parameter | Name:
C00588 | Resp. to max. speed at switching freq.
Data type: UNSIGNED_8
Index: 23987
d
= 5DB3
h
Response if the maximum speed for the set inverter switching frequency is reached (
C00018
)
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00590 | Resp. to switching frequency red.
Data type: UNSIGNED_8
Index: 23985
d
= 5DB1
h
Response to reduction of the inverter switching frequency (
C00018
)
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00592 | Resp. to CAN bus connection
Data type: UNSIGNED_8
Index: 23983
d
= 5DAF
h
Configuration of monitoring of the CAN interface (group 1)
System bus "CAN on board"
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C00592/1
0: No Reaction
Response to incorrect telegram for CAN communication
C00592/2
0: No Reaction
Response to "BusOff" (bus system switched off)
C00592/3
0: No Reaction
Response to warnings of the CAN controller
C00592/4
0: No Reaction
Response to communication stop of a CAN bus node
C00592/5
0: No Reaction
Response to an event in the case of monitoring via
heartbeat protocol
;
Read access
;
Write access
CINH
PLC STOP
No transfer
;
COM
MOT
Scaling factor: 1