8400 StateLine C | Reference manual
Commissioning
PC manual control
70
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
How to activate PC manual control:
1. If an online connection to the controller has not been established yet:
Go online.
2. Go to
Workspace
and change to the
Application parameters
tab.
3. Go to the
Overview
dialog level and click the "
PC manual control
" button.
• The following safety note is displayed first:
• Click the
Cancel
button to abort the action and close the dialog box.
• The
Timeout monitoring
input field serves to adapt the timeout for monitoring
the connection between the PC and the controller.
Note!
For activated PC manual control:
The online connection between the PC and the controller is monitored by the
controller.
• If the online connection is interrupted for longer than the set timeout (Lenze
setting: 2 s):
– Error response "Fault" is triggered, i.e. the motor becomes torqueless and is
coasting unless it already is at standstill.
– The "
Ck16: Time overflow manual control
" error message is entered into
the logbook.
PC manual control provides the
Motion Control Kernel
and the motor interface
with all required control signals and setpoint signals.
• The existing application (function block interconnection) is now decoupled
from these interfaces but will be processed as before and remains
unchanged.
• It does not matter what type of motor control is set in
C00006
.