Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
81
8400 StateLine C | Reference manual
Device control (DCTRL)
Device commands (C00002/x)
4.1.3
Save all parameter sets
If parameter settings are changed in the controller, those changes will be lost after mains
switching of the controller unless the settings have been saved explicitly.
The
C00002/11
= "1: On / start" device command saves the current parameter settings
safe against mains failure to the memory module of the controller.
How to save the parameter settings to the memory module:
Execute the "Save all parameter sets" device command:
C00002/11
= "1: On / start"
The storage process may take a couple of seconds. After the device command has
been called in
C00002/11
, dynamic status information ("Work in progress 20%"
"Work in progress 40%"
"Work in progress 60%", etc.) is returned.
Tip!
• This device command can also be activated via the
Toolbar
icon.
• The "
Load Lenze setting
" device command (
C00002/1
= "1: On / start") resets
the parameter settings to the delivery status of the device.
Note!
When the device is switched on, all parameters are automatically loaded from
the memory module to the main memory of the controller.
Observe the following to avoid data inconsistencies which cause errors when the
parameters are loaded from the memory module:
During the storage process:
• Do not switch off the supply voltage!
• Do not remove the memory module from the device!
The controller is currently provided with one data record for all parameters, i.e.
every parameter has a value. Several data records per controller are in
preparation.