8400 StateLine C | Reference manual
Function library
Function blocks | L_MPot_1
812
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
16.1.23.2 Deactivate motor potentiometer
When the motor potentiometer is deactivated by setting
bInAct
to TRUE, the
nOut_a
output signal responds according to the function selected via
Function
.
[16-12] Example: Deactivation of the motor potentiometer when the
Function
= 1 has been selected
When the motor potentiometer is deactivated,
nOut_a
is reduced to 0 % with the deceleration time
wTif
.
If it is activated again,
nOut_a
is increased again to
nLowLimit
with the acceleration time
wTir
.
nOut
_
a
t
t
TRUE
FALSE
bUp
t
TRUE
FALSE
b
D
o
w
n
nHighLimit
nLowLimit
0
wTir
wTif
wTir
t
TRUE
FALSE
b
I
nAct
wTif
wTif
0
1