8400 StateLine C | Reference manual
Function library
Function blocks | L_OffsetGainP_1
830
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
16.1.32
L_OffsetGainP_1
This FB can add an offset to an analog input signal and amplify it afterwards. Preferably to
be interconnected directly after the analog input terminals.
The internal calculations (addition and subtraction) are carried out with 32 bits without
overflow/underflow. Division is not remainder considered.
Offset and gain are selected via parameters.
The value provided at the
nOut_a
output is internally limited to ±199.99 %.
Inputs
Outputs
Parameter
Function
Identifier
Data type
Information/possible settings
nIn_a
INT
Input signal
Identifier
Data type
Value/meaning
nOut_a
INT
Output signal
• Internal limitation to ±199.99 %
Parameter
Possible settings
Info
C00670
-100.0000
100.0000 Gain factor
• High gain factor for further
processing of smallest input
signals.
• Please observe the difference
with regard to the gain factors of
other blocks in percent
(±199.99 %
≈
2).
• Lenze setting: 1.0000
C00696
-199.99
%
199.99 Offset
• Lenze setting: 0.00 %
/B2IIVHW*DLQ3B
Q2XWBD
Q,QBD
2IIVHW
*DLQ
&
&
nOut_a
nIn_a Offset
+
(
)
Gain factor
⋅
=
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com