8400 StateLine C | Reference manual
Function library
System blocks | LS_DisFree_a
860
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
16.2.8.1
Display of internal process factors in application units
This function extension is available from version 06.00.00!
In addition to the display in percent in
C00482/1...8
, for the first four analog signals
nDis1_a
...
nDis4_a
the configurable display parameters
C00487/1...4
are provided. Via
these display parameters, internal process variables can be displayed, e.g. on the keypad,
with an individual scaling and an individual unit.
Configuration of the display parameters (
C00487/1...4
):
[16-27] Formula for scaling the display
Example 1:
Input variable
nDis1_a
= 100 %
Offset 1 (
C00484/1
) = 0 %
Display factor 1 (
C00485/1
) = 123.45
Text 1 (
C00486/1
) = "bottles"
Example 2:
Input variable
nDis2_a
= 40 %
Offset 2 (
C00484/2
) = 35 %
Display factor 2 (
C00485/2
) = 20
Text 2 (
C00486/2
) = "kg"
Parameter
Possible settings
Info
C00484/1...4
-199.99
%
199.99 Offset 1 ... 4
• See formula
[16-27]
.
• Lenze setting: 0.00 %
C00485/1...4
-65536.0000
65536.0000 Display factor 1 ... 4
• Scaling of the input variable for
the display.
• See formula
[16-27]
.
• Lenze setting: 1.0000
C00486/1...4
String of digits
Text 1 ... 4
• For each display value, an
individual unit (e.g. "bottles") can
be set.
Application unit 1
nDis1_a [%] Offset 1 [%]
+
100 [%]
--------------------------------------------------------------------
Display factor 1 [text 1]
⋅
=
Application unit 1
100 [%] 0 [%]
+
100 [%]
---------------------------------------
123.45 [bottles]
⋅
123.45 bottles
=
=
Application unit 2
40 [%] 35 [%]
+
100 [%]
---------------------------------------
20 [kg]
⋅
15.00 kg
=
=