Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
99
8400 StateLine C | Reference manual
Device control (DCTRL)
Automatic restart after mains connection/fault...
4.3.2
Auto-start option "Inhibit at Lenze setting"
This function extension is available from version 06.00.00!
The
"Inhibit at Lenze setting" auto-start option configurable via bit 4 of
C00142
prevents
the change to the "
SwitchedOn
" status after the Lenze setting has been loaded and the
controller is enabled.
For a change to the "
SwitchedOn
" status, the controller enable must first be deactivated
after the Lenze setting has been loaded. Only if the controller is enabled again afterwards,
the status changes to "
OperationEnabled
":
[4-2]
Example 1: Behaviour with activated auto-start option "Inhibit at Lenze setting" (
C00142
: Bit 4 = "1")
[4-3]
Example 2: Behaviour with deactivated auto-start option "Inhibit at Lenze setting" (
C00142
: Bit 4 = "0")
n
Loading of the Lenze setting not possible since controller inhibit not set.
o
Controller inhibit via signal change by the user
p
Loading of the Lenze setting via device command
C00002/1
= "1"
q
Controller enable via signal change by the user
r
Controller inhibit and subsequent controller enable via signal change by the user
t
load
= time required for loading the Lenze setting
,QLW
5HDG\7R6ZLWFK2Q
6ZLWFKHG2Q
2SHUDWLRQ(QDEOHG
&
/$B1&WUOE&,QK
W
W
5)5
W
&
W
n
r
o
p
W
ORDG
q
n
Loading of the Lenze setting not possible since controller inhibit not set.
o
Controller inhibit via signal change by the user
p
Loading of the Lenze setting via device command
C00002/1
= "1"
q
Controller enable via signal change by the user
t
load
= time required for loading the Lenze setting
,QLW
5HDG\7R6ZLWFK2Q
6ZLWFKHG2Q
2SHUDWLRQ(QDEOHG
&
/$B1&WUOE&,QK
W
W
5)5
W
&
W
W
n
o
p
ORDG
q