8
Appendix
EDBC250SIO | 2.0
109
8.1.13
Errorclass CPU 1: 200A
h
and CPU 2: 201A
h
Designation
Value
Name
Errorclass
Index
200A
h
/ 201A
h
Object Code
VARIABLE
No. of Elements
0
Data Type
UNSIGNED8
Access
Read
PDO Mapping
no
Default Value
00000000
h
The table below explains the entries in object 200A
h
or 201A
h
"Errorclass".
Id
Explanation
0
No error
1
Serious or synchronization error
2
Internal communication error
3
I/O error
4
Error in ErrorHandler or at the outputs
5
Fatal error
8.1.14
System Uptime [s] 200C
h
Designation
Value
Name
System uptime [s]
Index
200C
h
Object Code
VARIABLE
No. of Elements
0
Data Type
UNSIGNED32
Access
Read
PDO Mapping
no
Units
sec
Default Value
No default Value
8.1.15
Temperature Warning 2016
h
Designation
Value
Name
Temperature warning
Index
2016
h
Object Code
VARIABLE
No. of Elements
0
Data Type
UNSIGNED8
Access
Read
PDO Mapping
no
Value
0°C – 55°C
= 0;
<0°C or >55°C = 1
Default Value
No default value