6
Installation and Operation
EDBC250SIO | 2.0
69
FSoE parameter
Parameter
Unit
Range
[Default]
Description / note
Test pulse duration input 2
µs
300 ... 1500
[500]
Test pulse length of input 2
Input filter of input 2
The digital test pulse output is interrupted for the set duration of every test
pulse. The Safety I/O-module checks whether the digital inputs may turn Null
and whether there are any short circuits to noise voltages on the signal line.
Adapt the test pulse duration to the peripherals you use.
Test pulse duration input 3
µs
300 ... 1500
[500]
Test pulse length of input 3
Input filter of input 3
The digital test pulse output is interrupted for the set duration of every test
pulse. The Safety I/O-module checks whether the digital inputs may turn Null
and whether there are any short circuits to noise voltages on the signal line.
Adapt the test pulse duration to the peripherals you use.
Test pulse duration output 0
µs
500... 1500
[800]
Test pulse length of input 0
The digital power output is interrupted for the set duration of every test pulse.
The Safety I/O-module checks whether the power outputs may be turned off
and whether there are any short circuits to noise voltages on the output line.
Adapt the test pulse duration to the load applied.
Test pulse duration output 1
µs
500... 1500
[800]
Test pulse length of input 1
The digital power output is interrupted for the set duration of every test pulse.
The Safety I/O-module checks whether the power outputs may be turned off
and whether there are any short circuits to noise voltages on the output line.
Adapt the test pulse duration to the load applied.
Test frequency input 0
Hz
0 ... 25
[1]
Test pulse frequency of input 0
Value "0" means without Test pulse
t
t
t
t
f