6
Commissioning
6.6
Initial switch-on
36
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.6
Initial switch-on
Establishing communication
• To establish communication, the inverter drive must be supplied with mains voltage.
• PROFINET communication requires voltage supply of the communication unit.
• If this is requirement is not met, the "CE04: MCI communication error" error message (error No.
01.0127.00002) is output. The error must be reset in the Inverter Drive, so that AS-i
communication can be established.
• The external voltage supply serves to maintain PROFINET communication if the main supply
fails.
• With mains connection (power ON), ...
• all parameters (codes) are read;
• the output data are set to '0'.
• Addressing can be effected automatically via the IO controller or manually via codes in the
»Engineer«.
• Addressing the inverter requires a valid IP configuration if communication between the PC/
»Engineer« and the inverter via PROFINET is to be established.