Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
73
12
Error messages
12.2
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFINET: Invalid module configuration [0x01bc6430]
PROFINET: Record parameter: Invalid read [0x01bc6501]
PROFINET: Record parameter: Invalid write [0x01bc6502]
PROFINET: Data output status bad [0x01bc6503]
PROFINET: Data_Exchange status quit [0x01bc6531]
PROFINET: Station name error [0x01bc6532]
Response
(Lenze setting printed in bold)
(
Adjustable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
A module or submodule does not comply with the
configuration of the Siemens STEP7 engineering tool.
Check module configuration.
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
Invalid parameter read access
Check configuration.
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
Invalid parameter write access
When reading back the data, the IO Controller has
requested a data length (number of data bytes) that is to
small.
Check configuration.
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Output data invalid.
• Connection to the Siemens STEP7 engineering tool
has been interrupted.
• Check configuration.
• Check cables and terminals.
Response
(Lenze setting printed in bold)
(
Adjustable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
The data exchange via PROFINET has been terminated.
• Also see the chapter "
Check cables and terminals.
Response
(Lenze setting printed in bold)
Setting:
not possible
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
Station name is not DNS-conform.
Use a DNS-compliant station name.