Commissioning
Setting the IP configuration of the Inverter Drive 8400 motec
34
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3.2
Setting via codes in the »Engineer«
You can also set the IP parameters manually in the »Engineer« under the
Settings
tab. The values
will be transferred to the corresponding codes.
How to activate changed settings in the »Engineer«:
1. Execute device command
C00002 = "11: Save all parameter sets"
.
The current IP configuration is stored in the memory module of the inverter.
2. Carry out a "Type 0 reset" for the
of the node, or switch the
voltage supply of the Communication Unit off and on again.
Settings
Description
IP Config Control
) of how the IP configuration is to be made:
•
0
: The IP configuration currently saved in the Communication Unit is
used.
•
1
: The IP configuration is assigned by a BOOTP server using the BOOTP.
•
2
: The IP configuration is assigned by a DHCP server using the DHCP.
IP Address
Setting of the IP address (
Subnet Mask
Setting of the subnet mask (
)
Gateway Address
Setting of the gateway address (
Multicast IP Start Address
Setting of the Multicast IP start address (
Setting the multicast configuration (
Multicast Config TTL Value
Setting of the multicast TTL value (