I/O data transfer (implicit messages)
I/O configuration with »RSLogix 5000« version 19 or lower
60
Lenze · Decentralised frequency inverter 8400 motec (EtherNet/IP™ option) · EDS84DMOTEIP EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5. Go to the "New Module" dialog window and define the properties of the newly added
device .
The terms "input" and "output" refer to the point of view of the scanner:
• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.
Settings for Lenze technology applications or user-definable parameter sets:
If you use a Lenze technology application or an individual parameter set in the inverter, you
can exchange up to 10 user-definable words (INT) via the MCI_OUT port by means of the
"Input = 111"
assembly object instance. With the
"Output = 110"
assembly object
instance, you can exchange up to 8 user-definable words (INT) via the MCI_IN port.
Go to
"Configuration" and enter the
Assembly instance "130"
and the
Size "0"
.