Connection via M12 connector
Control connections with M12 connectors
Via the digital inputs of the two M12 control connections, it is possible to switch between
different speeds and directions of rotation. Up to 5 different speed settings (e. g. creep speed
and normal speed in both directions, as well as stop) can thus be selected. In addition, the
operating state is indicated via a digital output.
NOTICE
In the "DI/DO-GND bridged" version, the masses of the control terminal X1 and X2 (GND-I and
GND-O) are connected to each other. If only one speed is used, the connection to X2 is
sufficient.
Control connection X1
1
2
4
3
M12 A coded X1
Contact
Name
Meaning
1
n.c.
2
DI2
Digital input 2
3
GND-I
Ground of digital input
4
DI1
Digital input 1
Control connection X2
1
2
4
3
M12 A coded X2
Contact
Name
Meaning
1
24V
24 V supply (DO1 supply)
2
DI3
Digital input 3 (reference X1;3 = GND-I)
4
DO1
Digital output 1
3
GND-O
Ground of digital output
Connection data - digital inputs for control connection X1/X2
Name
Supply voltage
Internal resistance
V
in
R
i
DC V
Ω
DI1
24 (19.2 ... 28.8)
5600
DI2
DI3
Product extensions
Motor connection
Connection via M12 connector
100